Skip to content
Auto-Start SPP, Bypass (variable unbalance)

SAZV · CAT. SF022

Auto-Start SPP, Bypass (variable unbalance)

Bypass-switch auto-start SPP with variable unbalance trip.

  • With variable unbalance trip voltage
  • With Auto-Manual-Bypass switch

Specifications

Rated supply voltage
415V, 3ø, 50Hz
Operating voltage range
200 to 456V AC
Power consumption
5VA (max.) at rated voltage (transformer-based supply)
Relay output contact
1NO, 5A at 250V AC (resistive)
Unbalance trip voltage setting
30 to 60V (variable)
Reset gap (hysteresis)
6 to 10V
ON delay time
30 ± 5 Sec.
Trip time delay
3 ± 1 Sec.
Resetting
Auto-reset
Indications
GREEN: Power ON / GREEN: Healthy / RED: Trip
Enclosure material
ABS / PA6 - 30% GF
Enclosure size (mm)
85 (H) x 45.5 (W) x 81 (D)
Housing type
Housing Type 'C'
Mounting
Only panel (surface) mounting (no DIN rail)
Mounting dimensions
77mm centre-to-centre; alternatively 68 x 37 mm
Mounting hardware
M3.5 or M4 screws: 2 Nos.
Termination
0.5mm² PVC insulated wires
Wire colour / size / length
Red / Yellow / Blue (1 each), Grey & Green (2 each); 0.5mm², 300mm each
Net weight
275 gms

Get in touch

Enquire about the Auto-Start SPP, Bypass (variable unbalance)

Your enquiry is pre-filled with catalogue code SF022. Add your voltage, output and quantity needs and we'll reply with the exact part number and availability.

Send an enquiry

Tell us the product or application and we'll get back within one business day.