Skip to content
Basic SPP (wired, 42-50V)

PMR-SFWN · CAT. SF006

Basic SPP (wired, 42-50V)

Basic preventer, 42-50V unbalance trip, PVC wire termination.

  • Basic Model
  • Unbalance trip 42 to 50V

Specifications

Rated supply voltage
415V, 3ø, 50Hz
Operating voltage range
190 to 456V AC
Power consumption
5VA (max.) at rated voltage (transformer-based supply)
Relay contact rating
5A at 250V AC (resistive)
Unbalance trip voltage setting
42 to 50V
Reset gap (hysteresis)
6 to 9V
Trip time delay
3 ± 1 Sec.
Indications
RED: Trip / GREEN: Healthy
Enclosure material
ABS / PA6 - 30% GF
Enclosure size (mm)
85 (H) x 45.5 (W) x 76 (D)
Housing type
Housing Type 'C'
Mounting
Surface / panel mounting only (no DIN rail)
Termination
0.5mm² PVC insulated wires
Wire colour / size / length
Red / Yellow / Blue for R,Y,B; Grey x2 for relay contact; 0.5mm², 300mm each
Net weight
250 gms

Get in touch

Enquire about the Basic SPP (wired, 42-50V)

Your enquiry is pre-filled with catalogue code SF006. Add your voltage, output and quantity needs and we'll reply with the exact part number and availability.

Send an enquiry

Tell us the product or application and we'll get back within one business day.